Papworth Hospital construction

Sika provides watertight solution for Papworth Hospital basement

  • 18 Apr 2016

A range of Sika’s waterproofing solutions have been applied to the new £140 million Papworth Hospital currently under construction in Cambridge.

The new 300-bed hospital is being developed by Skanska and will replace the existing Papworth Hospital on the Cambridge Biomedical Campus. It will become a specialised cardiothoracic hospital (relating to heart/chest or lungs) that will feature 7 operating theatres, a 46 bed critical care area, diagnostic and treatment facilities and a 24 bed day ward.

Waterproof basement solutions

A Sika Watertight Concrete System was installed by RC frame contractor Wheland and Grant in the hospital’s basement area to comply with BS 8102:2009 Grade 3, for habitable areas where no water penetration is acceptable.

Papworth Hospital constructionThe dual system comprised more than 2,000m3 of Sika Watertight Concrete and 16,000m2 of its SikaProof A-08 waterproofing membrane system. The combined system minimised the risk of water penetration to both the basement and ground floors, whilst the SikaProof A-08 also protected the building with an effective barrier against radon and methane gases.

Steve Wood, contracts manager at Whelan and Grant, commented on how the Sika system helped with a challenging installation. He explained: 

“There was a high water table on this project, so a dewatering system had to be kept running whilst the basement walls were being built. 

There was also the challenge of the excavation cut line being steep and close to the building which meant access to the basement walls was restricted. This had to be thought about and considered at all times when jointing and making good the SikaProof A-08 membrane.”

SikaProof A-08 membrane

SikaProof A is embossed with a unique grid pattern containing a sealant and a thin layer of fleece which forms a mechanical bond to the concrete as it cures. This offers an added layer of protection which bonds tightly to the surface of the concrete, forming miniature watertight compartments.

Any damage caused to the membrane is then contained within these compartments so that moisture or pressured water cannot spread between the membrane and the concrete structure.

Steve continued: “Liquid gas barriers were also used on the tops of the pile caps. As the basement raft slab formed the top of the pile cap, the SikaProof A-08 membrane stopped at the pile cap, lapping onto the Sikadur 32 liquid applied membrane which was on top of the pile cap.”

Watertight Concrete System

Sika also provided its Watertight Concrete System for below ground and basement construction. This utilises Sika admixtures to prevent water from migrating through the concrete. 

This is achieved by reducing the water/cement ratio, therefore increasing the density of the mix and minimising the size, volume and continuity of the concrete’s pores and filling the remaining pores.

The hospital is set to open in 2018 following the successful application of the Sika Waterproofing System.

Sika Limited
Watchmead
Welwyn Garden City
Hertfordshire
AL7 1BQ
Telephone: +44 (0) 1707 394444

Visit Sika's website

Leave a Reply

Latest news

BMBI
GEZE
Encon
SWA

SWA: A focus on Steel Window Association member West Leigh

Located in Charlton, South London, SWA member West Leigh was established during the Blitz, in 1943. During the destruction in London, the company helped in repairing windows and facades that had been damaged by bombings throughout the city.

Posted in Articles, Building Associations & Institutes, Building Industry News, Building Products & Structures, Building Services, Building Systems, Case Studies, Facades, Glass, Glazing, Restoration & Refurbishment, Retrofit & Renovation, Steel and Structural Frames, Walls, Windows